Item no. 750-667/000-003

Fail-safe 4/4 channel digital input/output; 24 VDC; 2 A; PROFIsafe V2.0 iPar; yellow

Description



The 75x-667/000-003 module is equipped with 4 power outputs (O1 .. O4) and 4 clock sensitive inputs (I1 .. I4). The sensors can be supplied directly with 24V, or fed by 2 differently clocked outputs (T1 ... T2).

The inputs connect potential-free, emergency-off switches with contacts, protection door switches, mode selectors, as well as both safety sensors and semiconductor outputs (e.g., light barriers, PLC outputs). The power outputs switch both DC13 resistive and inductive loads with up to a 2A-rated current without requiring any additional external circuit.

The power outputs operate in both bipolar (high-side/low-side switching) and unipolar (common potential on one side of the load) modes.

The modules monitor short-circuits, cross circuits and 24V voltage supply from separate sources. Both the monitoring and additional safety relevant parameters (e.g., operating modes, switching off test pulses, discrepancy or filter times) can be configured via WAGO-I/O-CHECK.

The configuration tool can be conveniently integrated into engineering systems supporting both CC2 and CC3 tool calling interfaces (TCI).

When exchanging modules, parameters are automatically downloaded into the control unit via PROFIsafe-compatible iPar server – depending on settings. The PROFIsafe address can be set using the DIP switch on the side of the module, or via WAGO-I/O-CHECK.

The modules support both PROFIsafe V1 (PROFIBUS) and V2 (PROFIBUS, PROFINET) protocols.

Individual input modules can be arranged in any combination when configuring the fieldbus node.

To protect the module against surge voltages (over-voltage protection acc. to IEC 61000-4-5), the filter module 750-626 or an external surge filter must be used for the 24V supply voltage.

Reference the product manual for further information (available in German and English).

Product details

Details

Technical Data

Number of digital inputs 4
Number of digital outputs 4
Total number of channels (module) 8
Achievable safety classes SIL 3; Cat. 4, PL e
Type of signal Voltage
Type of signal voltage DC 24 V
Sensor connection 4 x (sicherer Eingang mit Testpuls)
Actuator connection 4 x (fail-safe output with test pulse)
Input characteristic clock sensitive
Input characteristic Type 1
Input current per channel for signal (1) typ. 2.2 mA
Output switching design Power outputs
Output current per channel 2 A
Output current (module) 8 A
Output current short-circuit-protected
Switching frequency max. 50 Hz; Ohmsche Last
Switching frequency max. (2) 0.1 Hz; Induktive Last
Capacitive load for each channel O1 ... O4; 2.2 µF
Signal frequency max. 50 Hz
Switching frequency max. 50 Hz
Load type of the switching frequency Ohmsche Last
Test pulse duration min. 0 ms
Test pulse duration max. 500 ms
System supply voltage DC 5 V; via data contacts
Current consumption, system supply (5 V) 180 mA
System and sensor supply voltage )
Field supply voltage DC 24 V (-15 … +20 %); über Leistungskontakte (Einspeisung über Messerkontakt; Weiterleitung über Federkontakt)
Current consumption, field supply (module with no external load) 20 mA
Isolation 500 V System/Feld
Indicators LED (A-D) green/red: Status/Error I1 … I4; LED (I-M) green/red: Status/error O1 … O4;LED (E) red: Group error; LED (F-H) green/red: Diagnostics
Number of incoming power jumper contacts 2
Number of outgoing power jumper contacts 2
Current carrying capacity of the power jumper contacts 10 A

Connection data

Connection technology: In-/Outputs 16 x CAGE CLAMP®
Connection type (1) Inputs/Outputs
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 8 … 9 mm / 0.31 … 0.35 inch

Geometrical Data

Width 24 mm / 0.945 inch
Height 67.8 mm / 2.669 inch
Height from upper-edge of DIN-35 rail 60.6 mm / 2.386 inch
Depth 100 mm / 3.937 inch

Mechanical data

Type of mounting DIN-35 rail

Material Data

Color yellow
Housing material Polycarbonate, polyamide 6.6
Weight 104.404 g
Conformity marking CE

Environmental Requirements

Surrounding air (operating) temperature 0 … 55 °C
Surrounding air (storage) temperature -40 … 85 °C
Protection class IP20
Degree of pollution (5) 2 per IEC 61131-2
Operating altitude 0 … 2000 m
Mounting position horizontal (standing/lying) or vertical
Relative air humidity (no condensation) 95 %
Vibration resistance 4g per IEC 60068-2-6
Shock resistance 15g per IEC 60068-2-27
EMC immunity to interference acc. to EN 61000-6-2, marine applications
EMC emission of interference acc. to EN 61000-6-4, marine applications
Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 % 10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 % 25 ppm

Commercial data

Product Group 15 (Remote I/O)
Country of origin DE
GTIN 4050821038764

Approvals / Certificates

Ex-Approvals

Approval
Additional Approval Text
Certificate name
Language
Approval: ATEX
TUEV Nord Cert GmbH
Additional Approval Text EN 60079-0
Certificate name: TÜV 07 ATEX 554086 X en.
Approval: TUEV Nord
TUEV Nord Cert GmbH
Additional Approval Text IEC 60079-0
Certificate name: IECEx TUN 09.0001 X
Approval: UL
Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS)
Additional Approval Text ANSI/ISA 12.12.01
Certificate name: E198726 Sec.1

Country specific Approvals

Approval
Additional Approval Text
Certificate name
Language
Approval: KC
National Radio Research Agency
Additional Approval Text Article 58-2, Clause 3
Certificate name: MSIP-REM-W43-DI0750
Approval: TUEV Rheinland
TUEV Rheinland Industrie Service GmbH
Additional Approval Text -
Certificate name: No. 968/EZ 247.14/16

Ship Approvals

Approval
Additional Approval Text
Certificate name
Language
Approval: ABS
American Bureau of Shipping
Additional Approval Text -
Certificate name: 19-HG1821926
Approval: DNV GL
Det Norske Veritas, Germanischer Lloyd
Additional Approval Text -
Certificate name: TAA0000194
Approval: LR
Lloyds Register
Additional Approval Text -
Certificate name: 02/20026 (E6)
Approval: PRS
Polski Rejestr Statków
Additional Approval Text -
Certificate name: TE/2236/880590/19
Approval: RINA
RINA Germany GmbH
Additional Approval Text -
Certificate name: ELE066419XG

UL-Approvals

Approval
Additional Approval Text
Certificate name
Language
Approval: UL
UL International Netherlands B.V. (ORDINARY LOCATIONS)
Additional Approval Text UL 508
Certificate name: E175199 Sec.1

Downloads

Libraries

SISTEMA library

Gültigkeitsprüfung
V 0.0.8

CAD/CAE-Data

CAD data

3D Download 750-667/000-003

EPLAN

EPLAN Data Portal 750-667/000-003

WSCAD

WSCAD Universe 750-667/000-003

Device Files

Device Driver

Compatible products

Carrier rail

Item no.: 210-112
Steel carrier rail; 35 x 7.5 mm; 1 mm thick; 2 m long; slotted; according to EN 60715; "Hole width 25 mm
Item no.: 210-113
Steel carrier rail; 35 x 7.5 mm; 1 mm thick; 2 m long; unslotted; according to EN 60715
Item no.: 210-114
Steel carrier rail; 35 x 15 mm; 1.5 mm thick; 2 m long; unslotted; similar to EN 60715

Marking accessories

Supply module

Shield termination

System housing

Product family

750/753 Series I/O-System