Item no. 789-665

Ground resistance signaling module; Ground fault alarm via digital output; Supply voltage: 24 VDC; Module width: 18 mm

Item no. 789-665
Ground resistance signaling module
Please wait ...
Prices and availability
Your price per piece*
On request
PU (SPU): 1 Piece
The value you entered was rounded.
Not available for order under SPU!
The item is already added and will not be added again. If necessary, please adjust the quantity directly on the article.
Invalid input
1
Short description:
WAGO's module signals a value falling below a non-adjustable, asymmetric isolation resistance between +24 V or 0 V of the supply voltage and ground with a potential-free (Iso OK) contact and status LED. The Iso OK contact can be evaluated via a PLC.
This status is maintained until the next measurement interval.
Operation with Grounded Control Circuit (Functional Potential Equalization)
  • The module establishes an internal connection between the 0 V (X2.2) and ground (X2.1) connections via a semiconductor switch.
  • At 10 s intervals, this connection between 0 V and ground is interrupted for 0.5 s, and the isolation resistance between +24 V (X1.3) or 0 V (X2.2) of the supply voltage and earth (X2.1) is determined.
  • The grounding connection on the module does not meet the requirements of a protective earth terminal (PE). It serves as a functional ground. The measurement method does not involve the module establishing any permanent connection between 0 V and ground.

Operation with Ungrounded Control Circuit
  • In this operating mode, the semiconductor switch to establish a connection between 0 V (X2.2) and ground (X2.1) is deactivated. At 1 s intervals, the isolation resistance offset is determined for 0.5 s.
  • The module does not meet the requirements of an isolation monitoring device per EN 61557-8.

“Iso OK” Contact
  • The potential-free contact serves the purpose of supporting evaluation (e.g., via a PLC) of looming isolation faults.
  • This contact must not be used to switch safety-related products that could cause the circuit to switch off.
Item no. 789-665
Ground resistance signaling module
Please wait ...
Prices and availability
Your price per piece*
On request
PU (SPU): 1 Piece
The value you entered was rounded.
Not available for order under SPU!
The item is already added and will not be added again. If necessary, please adjust the quantity directly on the article.
Invalid input
1