This digital input module records binary signals from sensors operating in Zone 0+1 hazardous areas.
NAMUR sensors, optocouplers, mechanical contacts or other actuating elements can also be connected via intrinsically safe devices.
The WAGO I/O System 750 must be installed either in Zone 2 or in a non-hazardous area. Each sensor is supplied with a short-circuit-protected voltage of 8.2 V.
Indicators:
- Green LED (signal on)
Field and system levels are electrically isolated.