Item no. 750-823

Controller EtherNet/IP; 4th generation; 2 x ETHERNET; ECO

Item no. 750-823
Controller EtherNet/IP; 4th generation; 2 x ETHERNET;
Please wait ...
List price per piece*
On request
Price and availability after Login
Your price per piece*
On request
PU (SPU): 1 Piece
The value you entered was rounded.
Not available for order under SPU!
The item is already added and will not be added again. If necessary, please adjust the quantity directly on the article.
Invalid input
1
This controller can be used as a programmable controller within EtherNet/IP networks in conjunction with the WAGO I/O System.
The controller detects all connected I/O modules and creates a local process image. This process image may include a mixed arrangement of analog (word-by-word data transfer) and digital (bit-by-bit data transfer) modules.
Two ETHERNET interfaces and an integrated switch allow the fieldbus to be wired in a line topology, eliminating the need for additional network devices, such as switches or hubs. Both interfaces support autonegotiation and Auto-MDI(X).
The DIP switch configures the last byte of the IP address and may be used for IP address assignment.
The controller is designed for fieldbus communication in EtherNet/IP networks. It also supports a wide variety of standard ETHERNET protocols (e.g., HTTP(S), BootP, DHCP, DNS, SNTP, (S)FTP, SNMP).
An integrated Webserver provides user configuration options, while displaying the controller's status information.
The IEC 61131-3 programmable controller is multitasking-capable.

Product details

Details
Technical data
Communication EtherNet/IPTM
ETHERNET protocols FTP(S)
HTTP(S)
BootP
DHCP
DNS
SNTP
(S)FTP
SNMP
Visualization Web Visu
CPU 32 bits
Programming languages per IEC 61131-3 Instruction List (IL)
Ladder Diagram (LD)
Function Block Diagram (FBD), Continuous Function Chart (CFC)
Structured Text (ST)
Sequential Function Chart (SFC)
Programming environment WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Configuration options WAGO-I/O-CHECK
Web-based management
CODESYS Library
Baud rate (communication/fieldbus 1) 10/100 Mbit/s
Baud rate 10/100 Mbit/s
Transmission medium (communication/fieldbus) Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
Transmission performance Class D per EN 50173
Program memory 2 MB
Data memory 2 MB
Non-volatile software memory 32 Kbytes
Number of modules per node (max.) 250
Number of modules without a bus extension (max.) 64
Input and output (fieldbus) process image (max.) 1020 Worte/1020 Worte
Indicators LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user
Supply voltage (system) 24 VDC (-25 … +30 %); via pluggable connector
Input current (typ.) at nominal load (24 V) 300 mA
Power supply efficiency (typ.) at nominal load (24 V) 90 %
Power consumption (5 V system supply) 390 mA
Total current (system supply) 700 mA
Isolation 500 V system/field
Connection data
Connection technology: communication/fieldbus EtherNet/IPTM: 2 x RJ-45
Connection technology: system supply 2 x CAGE CLAMP®
Connection type (1) System supply
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 8 … 9 mm / 0.31 … 0.35 inch
Connection technology: device configuration 1 x Male connector; 4-pole
Physical data
Width 49.5 mm / 1.949 inch
Height 96.8 mm / 3.811 inch
Depth 71.9 mm / 2.831 inch
Depth from upper edge of DIN-rail 64.7 mm / 2.547 inch
Mechanical data
Weight 105.3 g
Housing material Polycarbonate; Polyamide 6.6
Environmental requirements
Surrounding air temperature (operation) 0 … 55 °C
Surrounding air temperature (storage) -25 … 85 °C
Protection type IP20
Pollution degree (5) 2 per IEC 61131-2
Operating altitude without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Relative humidity (without condensation) 95 %
Mounting position any
Mounting type DIN-35 rail
Vibration resistance 4g per IEC 60068-2-6
Shock resistance 15g per IEC 60068-2-27
EMC immunity to interference per EN 61000-6-2, marine applications
EMC emission of interference per EN 61000-6-3, marine applications
Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
Fire load 1.111 MJ
Permissible pollutant concentration H2S at a relative humidity < 75% 10 ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75% 25 ppm
Commercial data
Packaging type BOX
Country of origin DE
GTIN 4055143889094
Customs tariff number 8537109160
Approvals / Certificates
Ex-Approvals
Approval
Additional Approval Text
Certificate name
Language
Approval: ATEX
TUEV Nord Cert GmbH
Additional Approval Text EN 60079
Certificate name: TUEV_14_ATEX_148929_X
Approval: CCCEx
CQST/CNEx
Additional Approval Text CNCA-C23-01
Certificate name: 2020312310000213
Approval: IECEx
TUEV Nord Cert GmbH
Additional Approval Text IEC 60079
Certificate name: IECEx_TUN_14.0035_X
Approval: UL
Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS)
Additional Approval Text UL 121201
Certificate name: E198726 Sec.1
Country specific Approvals
Approval
Additional Approval Text
Certificate name
Language
Approval: KC
National Radio Research Agency
Additional Approval Text Article 58-2, Clause 3
Certificate name: MSIP-REM-W43-PFC750
Ship Approvals
Approval
Additional Approval Text
Certificate name
Language
Approval: ABS
American Bureau of Shipping
Additional Approval Text -
Certificate name: 19-HG1821926
Approval: DNV GL
Det Norske Veritas, Germanischer Lloyd
Additional Approval Text -
Certificate name: TAA0000194
Approval: LR
Lloyds Register
Additional Approval Text -
Certificate name: 02/20026 (E6)
Approval: RINA
RINA Germany GmbH
Additional Approval Text -
Certificate name: ELE066419XG
UL-Approvals
Approval
Additional Approval Text
Certificate name
Language
Approval: UL
Underwriters Laboratories Inc. (ORDINARY LOCATIONS)
Additional Approval Text UL 61010-2-201
Certificate name: E175199 Sec11
Downloads
Compatible products
Product family